Development of models and methodology for the reliability evaluation of two interconnected power systems

By: Dulce, Elvin D [author]
Contributor(s): Del Mundo, Rowaldo D [author]
Copyright date: 2018Subject(s): Electric power system In: Philippine Engineering Journal vol. 39, no. 2: (December 2018), pages 51-74Abstract: This study developed analytical and probabilistic models and methodology that simultaneously take into account the intermittency of wind power, the seasonal variation in hydropower, and the load forecast uncertainty, in evaluation the reliability of two interconnected power systems. The intermittency of wind power was incorporated by using a sliding window approach with a 7-hourperiod while the seasonal variation in hydropower was incorporated by considering the hourly generation. A seven-step approximation of the normal distribution was used for the load forecast uncertainty considerations. The Loss-of-Load Expectation (LOLE) in the Luzon Grid in 2014, when assisted by the Visayas Grid, increased from 53 hours/year to 95 hours/year when the intermittency of wind power, the seasonal variation in hydropower, and the load forecast uncertainty were considered. On the other hand, when the Luzon Grid is the assisting system, the LOLE in the Visayas Grid increased from 12 hours/year to 32 hours/year. A significant improvement was observed in the accuracy of the calculated LOLE in the two interconnected power system when the intermittency and the seasonal variation in the generation, and the load forecast uncertainty were simultaneously considered.
Tags from this library: No tags from this library for this title. Log in to add tags.
    Average rating: 0.0 (0 votes)
Item type Current location Home library Call number Status Date due Barcode Item holds
JOURNAL ARTICLE JOURNAL ARTICLE COLLEGE LIBRARY
COLLEGE LIBRARY
PERIODICALS
Not for loan
Total holds: 0

This study developed analytical and probabilistic models and methodology that simultaneously take into account the intermittency of wind power, the seasonal variation in hydropower, and the load forecast uncertainty, in evaluation the reliability of two interconnected power systems. The intermittency of wind power was incorporated by using a sliding window approach with a 7-hourperiod while the seasonal variation in hydropower was incorporated by considering the hourly generation. A seven-step approximation of the normal distribution was used for the load forecast uncertainty considerations. The Loss-of-Load Expectation (LOLE) in the Luzon Grid in 2014, when assisted by the Visayas Grid, increased from 53 hours/year to 95 hours/year when the intermittency of wind power, the seasonal variation in hydropower, and the load forecast uncertainty were considered. On the other hand, when the Luzon Grid is the assisting system, the LOLE in the Visayas Grid increased from 12 hours/year to 32 hours/year. A significant improvement was observed in the accuracy of the calculated LOLE in the two interconnected power system when the intermittency and the seasonal variation in the generation, and the load forecast uncertainty were simultaneously considered.

There are no comments for this item.

to post a comment.

Click on an image to view it in the image viewer